Cause: Air or other non-condensable gases in refrigerant system.
Action: Purge the condenser by using reclaim system, start and run system until it reaches running temperature. Purge again if necessary.
Cause: Condenser surface too small.
Action: Replace condenser with larger size.
Cause: Refrigerant system charge too large (liquid collection in condenser).
Action: Recover refrigerant until condensing pressure is normal. The sight glass must remain full.
Cause: Condensing pressure regulation set for too high a pressure.
Action: Set for the correct pressure.
Cause: Dirt on condenser surface. (AC)
Action: Clean condenser
Cause: Fan motor or blade defective or too small.
Action: Replace motor or fan blade or both
Cause: Air flow to condenser restricted.
Action: Remove air inlet obstruction or move condenser.
Cause: Incorrect air flow direction through condenser.
Action: Change rotation of fan motor. On condensing units, air must flow through condenser and then to compressor.
Cause: KVR condensing pressure regulator set too high.
Action: Change rotation of fan motor. On condensing units, air must flow through condenser and then to compressor.
Cause: Ambient temperature too high.
Action: Create fresh air inlet or move condenser.
Cause: Short-circuit between condenser fan airside pressure and suction sides.
Action: Install a suitable duct, possibly to outdoor air.
Cause: Bellows in KVR condensing pressure regulator might be leaking.
Action: Slowly loosen protective cap. If pressure or traces of refrigerant exist under the cap, there is a leak in the bellows. Replace valve.
Findings: Condensing pressure too low
Cause: Condenser surface too large.
Action: Establish condensing pressure regulation or replace condenser with a smaller one.
Cause: Low load on evaporator.
Action: Establish condensing pressure regulation.
Cause: Suction pressure too low, e.g. insufficient liquid in evaporator.
Action: Locate fault on line between condenser and thermostatic expansion valve.
Cause: Compressor suction and discharge valves might be leaking.
Action: Replace compressor valve plate (semi-hermetic compressor) or replace compressor (hermetic compressor)
Cause: Condensing pressure regulator set too low.
Action: Set condensing pressure regulator to correct pressure.
Cause: Un-insulated receiver placed too cold in relation to condenser (receiver acts as condenser).
Action: Move receiver or fit it with suitable insulating cover.
Cause: Air temperature too low. (AC)
Action: Establish condensing pressure regulation.
Cause: Air volume through condenser too large. (AC)
Action: Replace fan with smaller unit or establish motor speed regulation.
Cause: Water flow rate too high. (WC)
Action: Install WVFX automatic water valve or set existing valve correctly
Cause: Water temperature too low. (WC)
Action: Decrease water volume / flow by using a WVFX automatic water valve, for example
Cause: Water quantity too large. (WC)
Action: Set WV water valve for smaller water quantity, i.e. higher pressure.
Cause: WV water valve open because of defective lower diaphragm. (WC)
Action: Check water valve for cracks in diaphragm. Replace diaphragm. See spare parts catalogue*. There must be no pressure on bellows element during removal and refitting.
Cause: WV water valve cannot close because of dirt in the seat. Valve cone sticks because of dirt. (WC)
Action: Check water valve for dirt and clean it. Replace parts as necessary. See spare parts catalogue. There must be no pressure on bellows element during removal and refitting. Install a filter ahead of the water valve."
Findings: Condensing pressure erratic
Cause: Differential on start/stop pressure control for condenser fan too large. Can cause vapour formation in liquid line for some time after start of condenser fan because of refrigerant collection in condenser.
Action: Set differential on lower value or use valve regulation (KVD + KVR) or use fan motor speed regulation.
Cause: Thermostatic expansion valve hunting.
Action: Set thermostatic expansion valve for higher superheat or replace orifice with smaller size
Cause: Fault in KVR/KVD condensing pressure regulating valves (orifice too large).
Action: Replace valves with smaller size.
Cause: Consequence of hunting suction pressure.
Action: See "Suction pressure hunts".
Cause: Wrong sized or located check valve in condenser line.
Action: Check sizing. Mount check valve below condenser and close to receiver inlet.
Cause: WV water valve too large.(WC)
Action: Replace water valve with a smaller size.

0 Comments