Finding: Evaporator blocked by frost. Cause: Lack of or poor defrost procedure. Action: Install defrost system or adjus…
Read moreFinding: Burnt-out coil Cause: Incorrect voltage/frequency. (Coil cold with voltage on) Check coil data. Action: Replac…
Read moreFindings: Bubbles in sight glass after filter Cause: Pressure drops across filter too high. Action: Compare filter size…
Read moreFindings: Liquid level in receiver too high Cause: Partial blockage of a component in liquid line. Action: Find the c…
Read moreFindings: Filter drier cold, dew or frosting possible Cause: Partial blocking of dirt strainer in filter drier. Action:…
Read moreFindings: Condensing pressure too high Cause: Air or other non-condensable gases in refrigerant system. Action: Purge…
Read moreFinding : Compressor is too cold. Cause : Possibly flow of liquid refrigerant from evaporator to suction line and compr…
Read more